ESP-Modbus

Overview

The Modbus serial communication protocol is de facto standard protocol widely used to connect industrial electronic devices. Modbus allows communication among many devices connected to the same network, for example, a system that measures temperature and humidity and communicates the results to a computer. The Modbus protocol uses several types of data: Holding Registers, Input Registers, Coils (single bit output), Discrete Inputs. Versions of the Modbus protocol exist for serial port and for Ethernet and other protocols that support the Internet protocol suite. There are many variants of Modbus protocols, some of them are:

  • Modbus RTU — This is used in serial communication and makes use of a compact, binary representation of the data for protocol communication. The RTU format follows the commands/data with a cyclic redundancy check checksum as an error check mechanism to ensure the reliability of data. Modbus RTU is the most common implementation available for Modbus. A Modbus RTU message must be transmitted continuously without inter-character hesitations. Modbus messages are framed (separated) by idle (silent) periods. The RS-485 interface communication is usually used for this type.

  • Modbus ASCII — This is used in serial communication and makes use of ASCII characters for protocol communication. The ASCII format uses a longitudinal redundancy check checksum. Modbus ASCII messages are framed by leading colon (“:”) and trailing newline (CR/LF).

  • Modbus TCP/IP or Modbus TCP — This is a Modbus variant used for communications over TCP/IP networks, connecting over port 502. It does not require a checksum calculation, as lower layers already provide checksum protection.

Note

This documentation (and included code snippets) requires some familiarity with the Modbus protocol. Refer to the Modbus Organization’s with protocol specifications for specifics Protocol References.

Modbus Supported Communication Options

The Modbus library supports the standard communication options as per Modbus specification stated below.

Standard Modbus communication options

Modbus option

Description of the option

RTU communication

  • 1 start bit

  • 8 data bits, least significant bit sent first

  • 1 bit for even / odd parity-no bit for no parity

  • 1 stop bit if parity is used, 2 stop bits if no parity

  • Cyclical Redundancy Check (CRC)

ASCII communication

  • 1 start bit

  • 7-8 data bits, least significant bit sent first

  • 1 bit for even / odd parity-no bit for no parity

  • 1 stop bit if parity is used, 2 stop bits if no parity

  • Longitudinal Redundancy Check (LRC)

TCP communication

  • Communications between client (master) - server (slave) over TCP/IP networks

  • Connection uses the standard port 502

  • The frames do not require checksum calculation (provided by lower layers)

Some vendors may use subset of communication options. In this case the detailed information is clarified in the device manual and it is possible to override the standard communication options for support of such devices. Please refer to Slave Communication Options, Master Communication Options for more information.

Messaging Model And Data Mapping

Modbus is an application protocol that defines rules for messaging structure and data organization that are independent of the data transmission medium. Traditional serial Modbus is a register-based protocol that defines message transactions that occur between master(s) and slave devices (multiple masters are allowed on using Modbus TCP/IP). The slave devices listen for communication from the master and simply respond as instructed. The master(s) always controls communication and may communicate directly to one slave, or all connected slaves, but the slaves cannot communicate directly with each other.

Modbus segment diagram

Modbus segment diagram

Note

It is assumed that the number of slaves and their register maps are known by the Modbus master before the start of stack.

The register map of each slave device is usually part of its device manual. A Slave device usually permits configuration of its short slave address and communication options that are used within the device’s network segment.

The Modbus protocol allows devices to map data to four types of registers (Holding, Input, Discrete, Coil). The figure below illustrates an example mapping of a device’s data to the four types of registers.

Modbus data mapping

Modbus data mapping

Mapping Of Complex Data Types

As per section 4.2 of Modbus specification, “MODBUS uses a big-Endian representation for addresses and data items. This means that when a numerical quantity larger than a single byte is transmitted, the most significant byte is sent first”. The biggest official structure defined by the Modbus specification is a 16-bit word register, which is 2 bytes. However, vendors sometimes group two or even four 16-bit registers together to be interpretted as 32-bit or 64-bit values, respectively. It is also possible when the Modbus vendors group many registers together for serial numbers, text strings, time/date, etc. Regardless of how the vendor intends the data to be interpreted, the Modbus protocol itself simply transfers 16-bit word registers. These values grouped from registers may use either little-endian or big-endian register order.

Note

Each individual 16-bit register, is encoded in big-endian order (assuming the Modbus device abides by the Modbus specification). However, the 32-bit and 64-bit types naming conventions like ABCD or ABCDEFGH, does not take into account the network format byte order of frame. For example: the ABCD prefix for 32-bit values means the common Modbus mapping format and corresponds to the CDAB on network format (order in the frame).

Common Data Types Supported By Modbus Vendors

Table 1 basic types used by Modbus vendors

Type

Range

Format description

U8, I8 - Unsigned/Signed 8-bit type

(0 .. 255)/(-128 .. 127)

Common unsigned 8-bit type that is stored usually in one Modbus register. The value can be stored in HI or LO byte of the register or packed with the next byte into one 16 - bit register.

U16 - Unsigned integer 16-bit type

0 - 65535

Stored in one 16-bit register. The values can be stored with AB or BA endianness.

I16 - Signed integer 16-bit type

-32768 to 32767 is allowed.

Stored in one 16-bit register. The values can be stored with AB or BA forendiannessmat.

I32 - Signed long integer 32-bit type

-2147483648 to 2147483647 is allowed.

Stored in two consecutive 16-bit register. The values can be stored with ABCD - DCBA endianness (see below).

U32 - Unsigned long integer 32-bit type

0 to 4294967295 is allowed.

Stored in two consecutive 16-bit register. The values can be stored with ABCD - DCBA endianness.

U64 Unsigned Long long integers (Unsigned integer 64)

0 to 18446744073709551615 is allowed.

Stored in four consecutive 16-bit register. The values can be stored with ABCDEFGH - BADCFEHG endianness.

I64 Signed Long long integers (Signed integer 64)

-9223372036854775808 to 9223372036854775807 is allowed.

Stored in four consecutive 16-bit register. The values can be stored with ABCDEFGH - BADCFEHG endianness.

Floating point single precision 32-bit

1.17549435E-38 to 3.40282347E+38 is allowed.

Stored in two consecutive 16-bit register per IEEE754. The values can be stored with ABCD - DCBA endianness.

Floating point double precision 64-bit

+/-5.0E-324 to +/-1.7E+308 is allowed.

Stored in four consecutive 16-bit register per IEEE754. The values can be stored with ABCDEFGH - BADCFEHG endianness.

As showed in the table above the float and double types do not fit to the 16-bit register and reguire several consecutive registers be used to store the value. However, different manufacturers store the consecutive bytes in different order (not standardized). For example: The DCBA prefix means inversed Modbus format (BADC order on network format).

Table 2 Modbus byte order for extended types

Postfix

Format description

ABCD

Big endian, high order byte first

CDAB

Big endian, reversed register order (Little endian with byte swap)

BADC

Little endian, reversed register order (Big endian with byte swap)

DCBA

Little endian (Low order byte first)

The extended data types are used to define all possible combinations of groupped values are represented below and correspond to param_type field of the data dictionary as described in the table below:

Table 3 Modbus extended data types of characteristics

Type

Format type description (common format)

Format type (network format)

PARAM_TYPE_U8

compatibility type corresponds to PARAM_TYPE_U8_A

Unsigned integer 8 bit type

PARAM_TYPE_U16

Unsigned integer 16 bit type, corresponds to PARAM_TYPE_U16_AB

Little endian byte swap

PARAM_TYPE_U32

Default unsigned integer 32 bit type, corresponds to PARAM_TYPE_U32_ABCD

Little endian byte swap

PARAM_TYPE_FLOAT

Default unsigned integer 32 bit type, corresponds to PARAM_TYPE_FLOAT_ABCD

Little endian byte swap

PARAM_TYPE_ASCII

Default ASCII string format

Packed ASCII string data

PARAM_TYPE_BIN

Binary data type

Default type for binary packed data

PARAM_TYPE_I8_A

I8 signed integer in low byte of register, high byte is zero

I8 signed integer LO

PARAM_TYPE_I8_B

I8 signed integer in high byte of register, low byte is zero

I8 signed integer HI

PARAM_TYPE_U8_A

U8 unsigned integer written to low byte of register, high byte is zero

U8 unsigned integer LO

PARAM_TYPE_U8_B

U8 unsigned integer written to hi byte of register, low byte is zero

U8 unsigned integer HI

PARAM_TYPE_I16_AB

I16 signed integer, big endian

Big endian

PARAM_TYPE_I16_BA

I16 signed integer, little endian

Little endian

PARAM_TYPE_U16_AB

U16 unsigned integer, big endian

Big endian

PARAM_TYPE_U16_BA

U16 unsigned integer, little endian

Little endian

PARAM_TYPE_I32_ABCD

I32 ABCD signed integer, big endian

Little endian byte swap

PARAM_TYPE_I32_CDAB

I32 CDAB signed integer, big endian, reversed register order

Big endian

PARAM_TYPE_I32_BADC

I32 BADC signed integer, little endian, reversed register order

Little endian

PARAM_TYPE_I32_DCBA

I32 DCBA signed integer, little endian

Big endian byte swap

PARAM_TYPE_U32_ABCD

U32 ABCD unsigned integer, big endian

Little endian byte swap

PARAM_TYPE_U32_CDAB

U32 CDAB unsigned integer, big endian, reversed register order

Big endian

PARAM_TYPE_U32_BADC

U32 BADC unsigned integer, little endian, reversed register order

Little endian

PARAM_TYPE_U32_DCBA

U32 DCBA unsigned integer, little endian

Big endian byte swap

PARAM_TYPE_FLOAT_ABCD

Float ABCD floating point, big endian

Little endian byte swap

PARAM_TYPE_FLOAT_CDAB

Float CDAB floating point, big endian, reversed register order

Big endian

PARAM_TYPE_FLOAT_BADC

Float BADC floating point, little endian, reversed register order

Little endian

PARAM_TYPE_FLOAT_DCBA

Float DCBA floating point, little endian

Big endian byte swap

PARAM_TYPE_I64_ABCDEFGH

I64, ABCDEFGH signed integer, big endian

Little endian byte swap

PARAM_TYPE_I64_HGFEDCBA

I64, HGFEDCBA signed integer, little endian

Big endian byte swap

PARAM_TYPE_I64_GHEFCDAB

I64, GHEFCDAB signed integer, big endian, reversed register order

Big endian

PARAM_TYPE_I64_BADCFEHG

I64, BADCFEHG signed integer, little endian, reversed register order

Little endian

PARAM_TYPE_U64_ABCDEFGH

U64, ABCDEFGH unsigned integer, big endian

Little endian byte swap

PARAM_TYPE_U64_HGFEDCBA

U64, HGFEDCBA unsigned integer, little endian

Big endian byte swap

PARAM_TYPE_U64_GHEFCDAB

U64, GHEFCDAB unsigned integer, big endian, reversed register order

Big endian

PARAM_TYPE_U64_BADCFEHG

U64, BADCFEHG unsigned integer, little endian, reversed register order

Little endian

PARAM_TYPE_DOUBLE_ABCDEFGH

Double ABCDEFGH floating point, big endian

Little endian byte swap

PARAM_TYPE_DOUBLE_HGFEDCBA

Double HGFEDCBA floating point, little endian

Big endian byte swap

PARAM_TYPE_DOUBLE_GHEFCDAB

Double GHEFCDAB floating point, big endian, reversed register order

Big endian

PARAM_TYPE_DOUBLE_BADCFEHG

Double BADCFEHG floating point, little endian, reversed register order

Little endian

Note

The support for the extended data types should be enabled using the option CONFIG_FMB_MASTER_TIMEOUT_MS_RESPOND in kconfig menu.

The below diagrams show how the extended data types appear on network layer.

Modbus master response with ABCD frame

Modbus frame packaging examples (16-bit, 32-bit, 64-bit data)

The approach showed above can be used to pack the data into MBAP frames used by Modbus TCP as well as for other types with similar size.

The following sections give an overview of how to use the ESP_Modbus component found under components/freemodbus. The sections cover initialization of a Modbus port, and the setup a master or slave device accordingly: